Product description
The DT1104 Ptxx RS4 … MODBUS output Ptxx, resistance, and potentiometer transmitters allow the connection of Pt100 / Pt500 / Pt1000 temperature sensors, linear resistance, or potentiometers to their input.
When a Ptxx temperature sensor is connected, the output signal is proportional to the measured temperature; in the case of a resistor, to the measured resistance; and for a potentiometer, to the potentiometer position.
The measured and digitized output signal can be read from the device via communication channel.
The communication interface is RS485, and the protocol is MODBUS RTU/ASCII slave.
Up to 32 DT1104 Ptxx RS4 outputs can be daisy-chained and connected to a signal processing unit (PLC, DCS) on a single shared RS485 communication bus without using a line repeater.
Using DT1104 Ptxx RS4 signal converters offers several advantages:
- Eliminates the need for expensive PLC or DCS analog input modules.
- Only a single analog-to-digital signal conversion occurs between the sensor connected to the input and the signal processor, which significantly improves overall system accuracy. Transmission characteristics are outstanding: non-linearity is <0.01%, and the temperature coefficient is typically <25 ppm / °C.
- Field cabling costs are significantly reduced.
The galvanic isolation is three-way, meaning the input, output, and power supply are galvanically independent of each other. The working isolation voltage is 250 VACrms between the input, output, and power supply terminals.
Transmitter parameters can be configured via the USB port: input signal type, wiring configuration (2, 3, 4-wire), scaling, measurement time, and communication parameters. The value of the measured signal and potential error states can also be read.
The USB interface is galvanically isolated from the device input, allowing the configuration tool to be connected to the device even under operating conditions.
The configuration software can be downloaded free of charge from the manufacturer’s website, and the USB cable is included with the device.
Front-panel LED indicators provide information on the presence of the power supply and any error conditions.
Devices can be ordered with two types of power supply:
- DT1104 Pt xx RS4: 24 V ± 10% DC