DT1300 Intrinsically Safe Isolator / Power Supply

Product features

  • 0-20 mA / 4-20 mA / 0-10 V inputs
  • 0-20 mA / 4-20 mA / 0-10 V outputs
  • 17 VDC / 18 VDC transmitter supply
  • Non-linearity < 0.01%
  • Temperature-coefficient < 50 ppm / °C
  • 19-29 VDC supply voltage
  • TS-35 rail mounting, 12.5 mm width
  • 18 different types

Type designation

DT1300 intrinsically safe isolator power supply type designation

Product description

The DT1300 … Intrinsically Safe Isolators / Power Supplies provide signal transmission between transmitters operate in zone 0, zone 1 potentially explosive area and the signal processing units operate in the safe area.
The DT1300 … family galvanically isolate the input, the output and the power supply.
The intrinsically safe input signal may be 0-20 mA, 4-20 mA, 0-10 V, the output signal also may be 0-20 mA, 4-20 mA, 0-10 V.
The isolators available with two different transmitter supplies (17 VDC or 18 VDC). The safety data these two types differ considerably from each other, thus they can be flexibly matched to the various transmitters. The transmission parameters of the isolators are outstandingly good: the non-linearity is < 0.01% and the temperature coefficient is < 50 ppm / °C.
The supply voltage range is 19-29 VDC, thus the isolators are insensitive to the supply voltage change.

Technical specifications

Safety data:
The connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the standard EN 61010-1, taking into consideration the following:
Pollution level:2
Measurement category:II
Intrinsical safety data:
Certification:BKI 14 ATEX 0013
Protection marking:II (1)G [Ex ia Ga] IIC / IIB (-20 °C < Ta < +50 °C)
II (1)D [Ex ia Da] IIIC (-20 °C < Ta < +50 °C)
Safety data:
IICIICIIBIIB
TypeUo [V]Io [mA]Po [mW]Co [nF]Lo [mH]Co [nF]Lo [mH]
DT1300 ...1826956208836806
DT1300 ...1721160850165110005
Um:250 Veff
Input parameters:
Input signal:DC current or DC voltage
Ranges:see the type designation
Input resistance (current input):68 ohm
Input resistance (voltage input):1 Mohm
Overdrive:5%
Transmitter power supply:
DT1300 ...18:17.5 VDC @ 20 mA load
DT1300 ...17:16.5 VDC @ 20 mA load
Output parameters:
Output type:DC current or DC voltage
Ranges:see the type designation
Burden (current output):800 ohm (max.) at 17.5 V transducer supply
600 ohm (max.) at 16.5 V transducer supply
Load (voltage output):500 ohm
Error:0.05% @ Ta = 23 °C ±2 °C
Non-linearity:0,01% (max.)
Temperature-coefficient:50 ppm / °C (max.)
Supply-voltage effect:practically zero
Response time:10 ms (10-90%)
Galvanic isolation:
Operating isolation voltage:250 Veff (between the input, the output, and the supply voltage
terminals)
Test voltage:2500 VDC
Power supply:
Supply voltage:19-29 VDC
Consumption:2,2 W
Ambient conditions:
Operating temperature range:-20 - +50 °C
Relative humidity:90% (max., non-condensing)
Place of installation:safe area, cabinet
Installation:with 5 mm space, vertical position
Electromagnetic compatibility (EMC)
accordance with the standard EN 61326-1
Immunity:industrial area
Noise emission:Group 1, Class B
General data:
Housing:terminal assembly box, rail mounting on TS-35 rail,
material: polyamide PA6.6
Connection:plug-in screw terminal
Connection cable:0,25-1,5 mm2 (max.)
Dimensions:12.5 × 99 × 115 mm (width × height × depth)
Weight:0,15 kg
Protection:IP 20
Detailed information see in operating instructions. The Manufacturer maintains the right to change the technical data!

Downloads

Leaflet of productOperating InstructionATEX certificate

Application example

DT1300 intrinsically safe isolator power supply application example