The connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the standard EN 61010-1, taking into consideration the following: |
Pollution level: | 2 |
Measurement category: | CAT III |
Overcurrent protection in instalation: | 4 A |
Input parameters: |
Measured parameters: | U12, U23, U31, UL1, UL2, UL3, IL1, IL2, IL3, PL1, PL2, PL3, QL1, QL2, QL3, SL1, SL2, SL3, PFL1, PFL2, PFL3, φL1, φL2, φL3, ΣP, ΣQ, ΣS, ΣPF, f1, f2, f3, ρ12, ρ13, Pmom15, Pprog15, +EP1, -EP1, +EQ1, -EQ1, +EP2, -EP2, +EQ2, -EQ2, +EP3, -EP3, +EQ3, -EQ3, +ΣEP, -ΣEP, +ΣEQ, -ΣEQ |
Input voltage: | 0-125 VAC / 0-250 VAC resistor network (specified at ordering) |
Input current: | 0-5 AAC / 0-1 AAC galvanic isolated (specified at ordering) |
Overrange: | 2 × I, 1.2 × U, 300 V (max.) |
Short overrange (1 sec.): | 20 × I, 100 A (max.) |
Consumption of the input: | 0.5 VA (max.) |
Frequency range: | 40-80 Hz |
Error: | 0.2% |
Refreshing time: | 250 ms |
Temperature coefficient: | 25 ppm / °C (max.) |
Output parameters: |
Analogue outputs (optional): |
Output type: | 2 active current outputs (configurable, specified at ordering) |
Range: | 0-20 mA / 4-20 mA (scalable) |
Burden: | 500 ohm (max.) |
Refreshing time: | same as the measuring time (2 s) |
Overcurrent: | 20.8 mA |
Error: | < 4 uA (23 °C ±2 °C) < 40 uA (-20 - +60 °C) |
Burden resistance effect: | practically zero |
Pulse outputs (optional): |
Output type: | 2 galvanic isolated transistor, passiv switching transistor |
Rating: | 30 V, 50 mA |
MODBUS communication interface (optional): |
Interface type: | RS485, galvanic isolated |
Baud rate: | 300 / 600 / 1200 / 2400 / 4800 / 9600 / 14400 / 19200 / 32800 Baud |
Parity: | even / odd / none |
Protocol: | MODBUS RTU slave |
Address: | 1-255 |
Possible commands: | 3 (register read) |
Power supply: |
Supply voltage: | 24 VDC ±10% PQRM5100 11
230 V AC/DC ±10% PQRM5100 11 PS |
Power consumption: | 1.5 VA / 1 W |
Galvanic isolation: |
Current power measure input: | galvanic isolated, R < 20 mohm |
Voltage power measure input: | Resistordivider, R = 1.6 MOhm |
Operating isolation voltage: | 250 Veff(between measuring inputs and power supply input) |
Test voltage: | 4200 VDC (1 min.) (between measuring inputs and power supply input)
500 VDC (between output-power supply terminals) |
Ambient conditions: |
Operating temperature range: | 0-60 °C |
Storage temperature range: | 0-70 °C |
Relative humidity: | 90% (max., non condensing) |
Place of installation: | cabinet |
Electromagnetic compatibility (EMC)
accordance with the standard EN 61326-1 |
Immunity: | industrial area |
Noise emission: | Group 1, Class B |
General data: |
Housing: | terminal assembly box, rail mounting on TS-35 rail, material: polyamide PA6.6 |
Connection: | screw terminal |
Connection cable: | 4.5 mm2 (max.) |
Dimensions: | 22.5 × 108 × 114 mm (width × height × depth) |
Weight: | 0.4 kg (max.) |
Protection: | IP 20 |
|
Detailed information see in operating instructions. The Manufacturer maintans the right to change the technical data! |