DT1102 Switch Selectable Input-Output Galvanic Isolator

Product features

  • Selectable input/output ranges with front panel switches:
    0-20 mA / 4-20 mA / 0-10 V / 2-10 V input
    0-20 mA / 4-20 mA / 0-10 V / 2-10 V output
  • 3 way isolation
  • 20 VDC transmitter supply on the input for two wire transmitters
  • Non-linearity: < 0.01%
  • Temperature-coefficient: 25 ppm / °C typ.
  • 24 V ± 10% DC,
    230 V ± 10% AC/DC power supply
  • TS-35 rail mounting, 12.5 mm width

Type designation

DT1102 switch selectable I/O galvanic isolator-type designation

Product description

The DT1102 (PS) Switch Selectable Input-Output Galvanic Isolator provides signal transmission and conversion between DC current or DC voltage signal source and signal processing units.
The instruments feature complete 3-way isolation: the input, the output and the power supply are isolated from each other.
Continuous isolation voltage is 250 VACeff, between the input, the output and the power supply.
The instrument provides 20 VDC / 24 mA on the input for supplying passive two wire transmitters.
The DT1102 is particularly advantageous in industrial plants where different signal levels are in use.
The input/output ranges are selectable with front panel switches:

  • 0-20 mA / 4-20 mA / 0-10 V / 2-10 V input
  • 0-20 mA / 4-20 mA / 0-10 V / 2-10 V output

The instruments has two inputs:

  • current: 0 (4) mA – 20 mA*
  • voltage: 0 (2 ) V – 10 V*

The instruments has two outputs:

  • current: 0 (4) mA – 20 mA*
  • voltage: 0 (2) V – 10 V*

* it may be use only one input and one output at a time.

There are two power supply version: DT1102: 24 V ± 10% DC, DT1102 PS: 230 V ± 10% AC/DC.
The transmission parameters are outstandingly good: the non-linearity is < 0.01%, and the temperature coefficient is < 25 ppm / °C TYP.
Front panel LED’s indicate the power on state and the error states (input / output overrange, internal errors, …).

Technical specifications

Safety data:
The connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the standard EN 61010-1, taking into consideration the following:
Pollution level:2
Measurement category:II
Input parameters:
Input signal:DC current or DC voltage
Ranges:0-20 mA, 4-20 mA, 0-10 V, 2-10 V
Overload:400 mA (current input)
100 V (voltage input)
Input resistance (current input):10 ohm
Input resistance (voltage input):102 kohm
Transmitter power supply:
Voltage:> 20 V (20 mA load)
Overcurrent protection:25 mA
Output parameters:
Output signal:DC current or DC voltage
Ranges:0-20 mA, 4-20 mA (current output)
0-10 V, 2-10 V (voltage output)
Overdriving ability:22.5 mA (current output)
11 V (voltage output)
Load resistance:≤ 650 ohm (current output)
≥ 500 ohm (voltage output)
Output resistance:> 3 Mohm (current output)
< 0.5 ohm (voltage output)
Error of output:±0.05&#37 &#64 25 &#176C ±2 &#176C
Non-linearity:0.01% (max.)
Temperature coefficient:tip.: 25 ppm / °C; max.: 50 ppm / °C
Supply-voltage effect:practically zero
Settling time:250 ms (90%) / 300 ms (99%)
Galvanic isolation:
Working voltage:250 Veff (between the input, the output and the power supply terminals)
2500 VDC (1 min.)
Power supply:
Supply voltage:24 V &#177 10&#37 DC (DT1102)
230 V &#177 10&#37 AC/DC (DT1102 PS)
Power consumption:1.6 W (DT1102)
2.4 W / 3.8 VA (DT1102 PS)
Ambient conditions:
Operating temperature range:0-50 &#176C (-20 - +50 &#176C for customer request)
Relative humidity:90% (max., non-condensing)
Place of installation:cabinet
Mounting position:vertical (horizontal rail position)
Electromagnetic compatibility (EMC):
Accordance with the standard EN 61326-1
Noise emission:Group 1, Class B
Immunity:industrial area
ESD:4 kV / 8 kV surface / air
BURST:2 kV / 1 kV power / signal
SURGE:1 kV
Conducted RF immunity:3 Veff
Power failure bypass:20 ms @ 190-250 VAC
General data:
Housing:TS-35 rail mounting housing material: polyamide PA6.6
Connection:Pluggable screw-terminal
Connecting cable:1.5 mm2 (max.)
Dimensions:12.5 × 108 × 114 mm (width × height × depth)
Weight:0.15 kg
Protection:IP 20
Detailed information see in operating instructions. The Manufacturer maintans the right to change the technical data!

Downloads

Leaflet of productOperating Instruction

Application example

DT1102 switch selectable I/O galvanic isolator-application examle

Type selection and ordering