PQRM5100 11 Single-phase multifunction Power Transmitter

Product features

  • Measuring of 12 different parameters
  • 0-125 VAC / 0-250 VAC voltage input (CAT III)
  • 0-5 AAC / 0-1 AAC galvanic isolated current inputs (CAT III)
  • 2 × 0-20 mA / 4-20 mA galvanic isolated outputs
  • RS485 communication, MODBUS RTU / ASCII Slave protocol
  • 2 energy pulse outputs / limit outputs
  • Configurable from PC via USB port
  • 24 VDC ±10% or 230 V AC/DC ±10% power supply
  • 22.5 mm width, TS-35 rail mounting

Type designation

PQRM5100 11 single phase multifunction power transmitter-type designation

Product description

The PQRM5100 11 … Single-phase multifunction Power Transmitter suitable for the measuring of 12 different parameters of the singlephase power network:

  • The TRMS values of phase voltage and phase current
  • active power, reactive power, apparent power and power factor
  • + active energy, – active energy, inductive energy, – capacitive energy
  • frequency, phase angle.

The voltage inputs of the equipment are resistor networks (nonisolated) and the current inputs are isolated from the network with wideband current transformers. The current inputs 0-5 AAC or 0-1 AAC, and the voltage inputs 0-125 VAC / 0-250 VAC are in compliance with the requirements for measurement category CAT III.
The PQRM5100 11… is available with the following output options:

  • 2 × 0-20 mA / 4-20 mA galvanic isolated, scalable, active analog current outputs *
  • MODBUS RTU galvanic isolated communicatoin which makes possible the reading of all measurement values via the communication line, with a PLC or with a PC *.

(* only one option at the same time)

2 energy pulse outputs / limit outputs for limit-switching and for simple control tasks.
The measurement and output parameters are configurable from PC via USB port with the help of a user friendly configuration software. The configuration software is free of charge.
The PQRM5100 11 … has two power supply versions 24 VDC ±10% (PQRM5100 11 …) or 230 V AC/DC ±10%
(PQRM5100 11 … PS).

Technical specifications

Safety data:
The connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the standard EN 61010-1, taking into consideration the following:
Pollution level:2
Measurement category:CAT III
Overcurrent protection in instalation:4 A
Input parameters:
Measured parameters:URMS, IRMS, P, Q, S, PF, φ, f, +EP, -EP, +EQ, -EQ
Input voltage:0-125 VAC / 0-250 VAC resistor network (specified at ordering)
Input current:0-5 AAC / 0-1 AAC galvanic isolated (specified at ordering)
Overrange:2 × I, 1.2 × U, 300 V (max.)
Short overrange (1 sec.):20 × I, 100 A (max.)
Consumption of the input:0.5 VA (max.)
Frequency range:40-80 Hz
Error:0.2%
Refreshing time:250 ms
Temperature coefficient:25 ppm / °C (max.)
Output parameters:
Analogue outputs (optional):
Output type:2 active current outputs (configurable, specified at ordering)
Range:0-20 mA / 4-20 mA (scalable)
Burden:500 ohm (max.)
Refreshing time:same as the measuring time (2 s)
Overcurrent:20.8 mA
Error:< 4 uA (23 °C ±2 °C) < 40 uA (-20 – +60 °C)
Burden resistance effect:practically zero
Pulse outputs (optional):
Output type:2 galvanic isolated transistor, passiv switching transistor
Rating:30 V, 50 mA
MODBUS communication interface (optional):
Interface type:RS485, galvanic isolated
Baud rate:300 / 600 / 1200 / 2400 / 4800 / 9600 / 14400 / 19200 / 32800 Baud
Parity:even / odd / none
Protocol:MODBUS RTU slave
Address:1-255
Possible commands:3 (register read)
Power supply:
Supply voltage:24 VDC ±10% PQRM5100 11
230 V AC/DC ±10% PQRM5100 11 PS
Power consumption:1.5 VA / 1 W
Galvanic isolation:
Current power measure input:galvanic isolated, R < 20 mOhm
Voltage power measure input:resistordivider, R = 1.6 MOhm
Operating isolation voltage:250 Veff (between measuring inputs and power supply input)
Test voltage:4200 VDC (1 min.) (between measuring inputs and power supply input)
500 VDC (between output-power supply terminals)
Ambient conditions:
Operating temperature range:0-60 °C
Storage temperature range:0-70 °C
Relative humidity:90% (max., non condensing)
Place of installation:cabinet
Electromagnetic compatibility (EMC):
accordance with the standard EN 61326-1
Immunity:industrial area
Noise emission:Group 1, Class B
General data:
Housing:terminal assembly box, rail mounting on TS-35 rail, material: polyamide PA6.6
Connection:screw terminal
Connection cable:4.5 mm2 (max.)
Dimensions:22.5 × 108 × 114 mm (width × height × depth)
Weight:0.17 kg (max.)
Protection:IP 20
Detailed information see in operating instructions. The Manufacturer maintans the right to change the technical data!

Downloads

Leaflet of productOperating Instructions

Application example

PQRM5100 11 single phase multifunction power transmitter-application example 1

PQRM5100 11 single phase multifunction power transmitter-application example 2

RS485 bus topology

PQRM5100 11 single phase multifunction power transmitter application example

 

 

 

Type selection and ordering

Login to see prices