DT4226 Process Indicator

Product features

  • 0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V inputs
  • large, 5 digit LED display (101 mm character height)
  • adjustable brightness
  • readable even at a 50 m distance
  • menu driven setting, via front panel switches
  • 0.03% accuracy
  • 24 VDC ±10% or 230 V AC/DC ±10% power supply
  • 656 × 150 × 45 mm wall mount instrument

Product description

The DT4226 … Process Indicator enable linear process variables (0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V) to be displayed in engineering units on the place of installation. Any optional display range can be assigned to the input signal range.
Large 5 digit, 101 mm height LED display with adjustable brightness make process value easily visible at a 50 m distance.

DT4226 process indicator distance of visibility

The functional parameters can be set by membrane push-buttons on the front panel of the device, through a simple menu system: input selection, averaging of input signals, scaling, display refresh rate, etc. The settings are protected by a two-level password against unauthorised manipulation.
The instruments has two power supply versions: 24 VDC ±10% (DT4226 …) or 230 V AC/DC ±10% (DT4226 … PS)
The DT4226 … is housed in a metal case with IP40 protection for installation on a flat surface (e.g. wall).

Technical specifications

Safety data:
The inputs and the connection terminals of the supply voltages are isolated from each other, the isolation is in compliance with the standard EN 61010-1, taking into consideration the following:
Pollution level:2
Measurement category:II
Input parameters:
Input signal:DC current or DC voltage
Measurement range:0-20 mA / 4-20 mA / 0-10 V / 2-10 V / 0-5 V
Overrange:±50 mA (current input), ±200 V (voltage input)
Measuring parameters:
Characteristics:linear
Sampling:12 measurement / sec.
Number of averaged samples:1 / 2 / 4 / 8 / 16 / 32 / 64 (adjustable)
Error of displayed value:0.03% (Ta = 23 ˚C ±2 ˚C)
Temperature-coefficient:40 ppm / ˚C
Display:
Display unit:5 digit LED
Character height:101 mm
Display color:red
Brightness:adjustable between 10% - 100% in increments of 10%
Display:5 digit (+values), 4 digit (-values), negative sign, decimal point
Manual controls:
Manual controls:3 membrane push-buttons on the front cover
Power supply:
Supply voltage:24 VDC ±10% (DT4226 …)
230 V AC/DC ±10% (DT4226 ... PS)
Consumption:5 W (DT4226 …)
6 W (DT4226 ... PS)
Ambient conditions:
Operating temperature range:0 - +50 °C
Storage temperature range:-25 - +70 °C
Relative humidity:90% (max., non condensing)
Place of installation:indoor
Electromagnetic compatibility (EMC)
accordance with the standard EN 61326-1
Immunity:industrial area
Noise emission:Group 1, Class B
General data:
Housing:wall mount instrument
Connection:GM 209 NJ valve connector (power supply)
GDM 2009 valve connector (signal input)
Connection cable:0.25-1.5 mm2 (max.)
Dimensions:656 × 150 × 45 mm (width × height × depth)
Weight:3.4 kg
Protection:IP 40
Detailed information see in operating instructions. The Manufacturer maintans the right to change the technical data!

Downloads

Leaflet of product

Type selection and ordering

Login to see prices