DT1623 Ix AC current transmitters up to 60 A with frequency output

Features

  • 3 versions, 6 measuring ranges:
    0–5 AAC / 0–1 AAC *
    0–20 AAC / 0–10 AAC *
    0–60 AAC / 0–40 AAC *
    * measuring range selectable with switch
  • True RMS converter
  • CAT III measurement category
  • 400-2000 Hz frequency output
  • 0.5% accuracy
  • 24 VDC power supply
  • 17.5 mm wide, rail-mountable

Type designation

DT1623-Ix-type designation

Product description

The DT1623 Ix… AC current transmitters produce a square wave output with a frequency range of 400–2000 Hz,
proportional to the true root mean square (TRMS) of the input signal, for the processing unit.
By using the frequency output – in the case of a PLC signal processor – a costly analog input can be replaced with a
counter input.
The devices can be operated with a 24 VDC power supply.
The inputs of the transmitters are separated from the network to be measured by a broadband measuring transformer.
The inputs comply with the requirements of the CAT III measurement category.
The devices can be ordered in three versions with 6 measuring ranges, according to the type table above. Within the given type, the measuring range can be selected with the front-panel “Hi-Lo” switch.
The inputs can be permanently overdriven up to twice the nominal measuring range.
In the I5/1 measuring range version, the current to be measured can be connected via a terminal block, in the higher measuring ranges, the current to be measured wire must be threaded through the opening in the box.
A green indicator on the front panel indicates the operating status of the device, a continuous light indicates correct operation, a flashing light indicates an error status.
The device is designed as a terminal block, width: 17.5 mm.
The transmitters fully comply with the requirements of the EN 60688 standard.

Technical specifications

Safety data:
The input and output connection terminals are separated from each other, the separation complies with the requirements of EN 61010-1, taking into account the following:
Pollution level:2
Measurement category:CAT III
Input parameters:
Input signal:AC current
Measuring ranges:see the type designation
Conversion characteristics:true RMS
Continuous overcurrent:2 × I
Short time overcurrent (1 sec):20 × I
Input consumption:0.25 VA (max.)
Frequency range:40–400 Hz
Output parameters:
Output signal:frequency (square wave)
Output range:400–2000 Hz
Settling time:500 ms (10–90%)
Output signal error:< 0.5%
Output signal levels:Lo: < 0.2 V Hi: > 21 V (Rt: 2–20 kohm)
Temperature coefficient:< 25 ppm / °C (0–60 °C)
Frequency dependence:0.3% max. (40–400 Hz)
Supply voltage dependence:practically zero
Power supply:
Supply voltage:24 VDC ± 10%
Ambient conditions:
Operating temperature range:0–60 °C (-20–60 °C, on customer request)
Relative humidity:90% (max., non condensing)
Place of installation:cabinet
Recommended mounting position:vertical (horizontal rail position)
Electromagnetic compatibility (EMC):
Accordance with the standard EN 61326-1:
Noice emission:Group 1, Class B
Immunity:Industrial area
General data:
Housing:TS-35 rail mounting housing material: polyamide PA6.6
Connection (output):screw terminal
Connection (input):screw terminal < 10 AAC
through connection > 10 AAC
Through connection:10 mm2 (≤ 40 AAC)
16 mm2 (> 40 AAC)
Dimensions:17.5 × 104 × 115 mm (width × height × depth)
Weight:0.100...0.125 kg
Protection:IP 20